SIL
Safety Integrity Level
A measure of how much risk reduction a safety function delivers — SIL 1 is 10 to 100 times, SIL 3 is 1,000 to 10,000. It is a property of the complete function from sensor to final element, not of any single device. A 'SIL 2 transmitter' is an ingredient, not a result.