SIL

Safety Integrity Level

Instrumentation & Control

A measure of how much risk reduction a safety function delivers — SIL 1 is 10 to 100 times, SIL 3 is 1,000 to 10,000. It is a property of the complete function from sensor to final element, not of any single device. A 'SIL 2 transmitter' is an ingredient, not a result.

Explained in depth

Related terms

← All 148 terms